Pick the smallest size whose rated current covers the load, then check the drop: ΔU = 2 × length × current × resistance per length for single phase. Keep it within 3 % on a branch circuit. If it is over, go up a size.
Calcular
Calculadora de seção de cabo
Seção do cabo de cobre pela corrente, comprimento e queda de tensão.
Calculadora de seção de cabo →Check 1: current
In the United States, NEC Table 310.16 gives the ampacity of copper conductors. For the small sizes, NEC 240.4(D) also caps the breaker: 15 A on 14 AWG, 20 A on 12 AWG, 30 A on 10 AWG. A load that runs for three hours or more counts as continuous, and the wire must carry 125 % of it (NEC 210.19(A)(1)).
In Germany and much of Europe, DIN VDE 0298-4 gives the current-carrying capacity Iz by installation method: in insulation, in conduit, on the wall, in free air. The breaker In must sit between the load current and Iz: Ib ≤ In ≤ Iz.
| Size | Ampacity 60 °C | Ampacity 75 °C | Breaker limit |
|---|---|---|---|
| 14 AWG | 15 A | 20 A | 15 A |
| 12 AWG | 20 A | 25 A | 20 A |
| 10 AWG | 30 A | 35 A | 30 A |
Metric copper with PVC insulation, on a wall (method C), two loaded conductors, 30 °C (ABB Table 2): 1.5 mm² 19.5 A, 2.5 mm² 27 A, 4 mm² 36 A. In thermal insulation or in conduit the values are lower.
Check 2: voltage drop
Current flows out on one conductor and back on the other, so a single-phase run of length L has 2 × L of wire. The drop is that length times the current times the resistance per length. For three phase use √3 instead of 2.
- NEC informational note: not more than 3 % on the branch circuit and 5 % for feeder and branch together.
- Germany (DIN 18015-1, as given by ABB): 3 % behind the meter.
- Resistance rises with temperature. The calculator uses 75 °C values from NEC Chapter 9 Table 8 for AWG and 70 °C, the limit of PVC insulation, for metric sizes.
Worked example: 120 V, 16 A, 100 ft
A 20 A circuit to a workshop, 100 ft one way, carrying 16 A.
- 12 AWG carries 20 A, so it passes the current check.
- Drop on 12 AWG (1.93 Ω per 1,000 ft): 2 × 100 × 16 × 1.93 / 1,000 = 6.2 V, 5.1 % of 120 V. Too much.
- 10 AWG (1.21 Ω): 3.9 V, 3.2 %. Still over 3 %.
- 8 AWG (0.778 Ω): 2.5 V, 2.1 %. This is the size the drop asks for.
Worked example: 230 V, 16 A, 25 m
A socket circuit to a garden building, 25 m one way, 16 A.
- Resistance at 70 °C: R20 × (1 + 0.00393 × 50), about 1.2 times the 20 °C value.
- 1.5 mm² (12.1 Ω/km at 20 °C): 2 × 25 × 16 × 14.5 / 1,000 = 11.6 V, 5.0 %.
- 2.5 mm² (7.41 Ω/km): 7.1 V, 3.1 %. Just over 3 %.
- 4 mm² (4.61 Ω/km): 4.4 V, 1.9 %. Passes.
As a check of the method, ABB's table gives 34 m as the longest three-phase run of 1.5 mm² at 16 A and 400 V for a 3 % drop. With the conductor at 30 °C the formula gives the same 34 m.
Sizing a cable is the first step. The connection itself, the protection and the test belong to a qualified electrician.
Perguntas
What size wire for 20 amps at 100 feet?
For a 16 A load at 120 V, 8 AWG keeps the drop near 2 %. 12 AWG carries the current but drops about 5 %.
What voltage drop is acceptable?
The NEC recommends not more than 3 % on a branch circuit and 5 % in total. In Germany 3 % is the usual limit behind the meter.
Why does a longer cable need a thicker wire?
Resistance grows with length. Thicker copper has less resistance per metre, which keeps the drop down.
Is 2.5 mm² enough for 16 A?
For the current, yes, in most installation methods. For a long run, check the drop: at 16 A and 230 V, 2.5 mm² reaches 3 % at about 24 m.
Calcular
Calculadora de seção de cabo
Seção do cabo de cobre pela corrente, comprimento e queda de tensão.
Calculadora de seção de cabo →Fontes
- [1]Kabel- und Leitungsdimensionierung (2CDC400027D0104 Rev. E, 2023-10), after DIN VDE 0298-4 and DIN VDE 0100-430. ABB Stotz-Kontakt. Table 2: current-carrying capacity Iz of copper PVC cables at 30 °C ambient for installation methods A1, A2, B1, B2, C and E, two or three loaded conductors, 1.5 to 50 mm². Rule Ib ≤ In ≤ Iz. 3 % voltage drop behind the meter (DIN 18015-1); Table 11 (1.5 mm², 16 A, 400 V: 34 m at 3 %) as a check of the drop formula.. Conferido em 10 de novembro de 2026
- [2]Conductor resistance (IEC 60228 / DIN EN 60228, class 1 and 2). Bayka. Maximum DC resistance of plain copper conductors at 20 °C: 12.1 Ω/km for 1.5 mm² down to 0.387 Ω/km for 50 mm².. Conferido em 10 de novembro de 2026
- [3]Conductor resistance (temperature correction after IEC 60228 Annex B). Electrical Cable Engineering. R(t) = R20 × (1 + 0.00393 × (t − 20)) for annealed copper.. Conferido em 10 de novembro de 2026
- [4]Ampacity chart (NEC Table 310.16, copper, not more than three current-carrying conductors, 30 °C ambient). Cerrowire. Allowable ampacity of copper conductors 14 AWG to 1/0 AWG in the 60 °C and 75 °C columns.. Conferido em 10 de novembro de 2026
- [5]NEC Chapter 9, Table 8: Conductor Properties. NFPA (copy hosted by NECA-IBEW Electricians). DC resistance of uncoated copper at 75 °C in Ω per 1,000 ft: 14 AWG 3.07 (solid) to 1/0 AWG 0.122.. Conferido em 10 de novembro de 2026
- [6]National Electrical Code Basics: Sizing and Protecting Branch Circuit Conductors (L. Mari, 2022-06-07). EEPower. NEC 240.4(D): overcurrent protection of copper conductors not more than 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG. 210.19(A)(1): conductors carry the noncontinuous load plus 125 % of the continuous load. 110.14(C): 60 °C column for equipment rated 100 A or less unless marked for 75 °C.. Conferido em 10 de novembro de 2026
- [7]Voltage Drop Limitations on Branch Circuits (M. Holt, 2015-05-05). EC&M. NEC 210.19(A) Informational Note No. 4: not more than 3 % on the branch circuit and 5 % for feeder and branch circuit together.. Conferido em 10 de novembro de 2026