Insulation thickness is not a matter of picking a number that sounds right. It follows from the target, the material's conductivity and what the wall already has.

Updated November 10, 2026

Short answer

Thickness = needed R × λ. To reach U = 0.24 W/(m²K) on a bare wall you need R = 4.0 m²K/W from the insulation, which is 140 mm (5.5 in) of a board with λ 0.035 W/(mK).

Calculate it

Insulation thickness calculator

How many millimetres you need to reach a target U-value.

Insulation thickness calculator →

U-value, R-value and lambda

BR 443, the BRE conventions for U-value calculations, defines the resistance of one layer as R = d / λ. Here d is the thickness in metres and λ (lambda) is the design thermal conductivity of the material in W/(mK). The lower the lambda, the thinner the layer for the same resistance. BR 443 prefers the manufacturer's declared value where there is one.

The U-value is the reciprocal of the total resistance: U = 1 / (Rsi + R1 + R2 + … + Rse). A lower U-value means less heat loss. The sum applies to homogeneous layers; studs or other material bridging the insulation are not part of the calculator's simple sum.

In the US, R-value is given in h·ft²·°F/Btu. One such unit is 0.1761 m²K/W, so R-22.7 is 4.0 m²K/W. A board of λ 0.035 W/(mK) gives about R-4.1 per inch.

The surface resistances you must include

Still air on both faces of the element adds resistance of its own. BR 443 gives these values in m²K/W, depending on the direction of heat flow:

Surface resistances in BR 443 (normal emissivity)
ElementHeat flowRsiRseRsi + Rse
WallHorizontal0.130.040.17
RoofUpwards0.100.040.14
FloorDownwards0.170.040.21

The horizontal values apply to heat flow within 30° of horizontal, and these surface resistances are for surfaces in contact with still air.

Targets from the German GEG

Anlage 7 of the Gebäudeenergiegesetz sets maximum U-values for residential buildings when an element is renewed. These are the figures the calculator offers as ready-made targets:

GEG Anlage 7, residential buildings
ElementMaximum U, W/(m²K)
External walls0.24
Pitched roofs, top-floor ceilings, walls to unheated roof spaces0.24
Flat roofs with waterproofing0.20
Walls and ceilings to unheated rooms (not roof spaces)0.30

Outside Germany these are not legal requirements, only published figures you can use as a target. Your local code or an energy-grant programme may ask for something different, so check it before you order.

Worked example: bare wall

Target U = 0.24, so the total resistance is 1 / 0.24 = 4.167 m²K/W. Take away the wall surfaces (0.17) and the insulation must supply 3.997 m²K/W. Thickness = 3.997 × λ:

Insulation needed to reach U = 0.24 on a wall with nothing else in the build-up
λ, W/(mK)Thickness, mmThickness, in
0.0301204.7
0.0351405.5
0.0401606.3

The lambda values here are sample inputs, not product data. Use the figure printed on the board you are buying.

When the wall already has layers

Layers that stay in place each add d / λ, and the new insulation only has to make up the rest. If the existing layers add 0.50 m²K/W, the wall needs 3.997 − 0.50 = 3.497 m²K/W of new insulation, which is 122 mm at λ 0.035. Boards are sold in set thicknesses, so round up to the next size: 120 mm would fall short, 140 mm clears the target.

For a flat roof at U = 0.20 the numbers change in two ways: the target resistance is 5.0 m²K/W and the roof surfaces add 0.14, so 4.86 m²K/W has to come from the insulation, or 170 mm at λ 0.035. If a wall already meets the target, the answer is zero. The calculator says so instead of showing a negative thickness.

You can also aim for an R-value of the insulation alone instead of a U-value. Thickness is then R × λ without any surface resistance or existing layers.

New insulation, λ 0.035 122 → 140 mmExisting wall R 0.50 m²K/WR 3.497 m²K/W
With existing layers worth 0.50 m²K/W, the new board has to supply only the rest: 3.997 − 0.50 = 3.497 m²K/W, or 122 mm at λ 0.035. Round up to 140 mm.

Questions

How thick must insulation be to reach U = 0.24?

On a wall with no other insulating layers, about 140 mm (5.5 in) at λ 0.035 W/(mK), 120 mm at 0.030 and 160 mm at 0.040. Existing layers reduce this.

What is lambda?

The thermal conductivity of the material in W/(mK): how much heat passes through one metre of it for each kelvin of temperature difference. BR 443 prefers the manufacturer's declared value.

How do I convert R-value to a U-value?

Add the surface resistances and every layer's R, then take the reciprocal. In US units, multiply the R-value by 0.1761 first to get m²K/W.

Which U-value does the GEG require for a flat roof?

Anlage 7 lists 0.20 W/(m²K) for flat roofs with waterproofing when the element is renewed in a residential building. Pitched roofs and top-floor ceilings are 0.24.

Should I round up the thickness?

Yes, to the next board thickness you can actually buy. Rounding down leaves the wall above the target U-value.

Calculate it

Insulation thickness calculator

How many millimetres you need to reach a target U-value.

Insulation thickness calculator →

Sources

  1. [1]Conventions for U-value calculations, BR 443 (2019 edition). BRE, Brian Anderson and Ludmilla Kosmina. U = 1 / ΣR after BS EN ISO 6946. Surface resistances in m²K/W: walls (horizontal flow) Rsi 0.13, Rse 0.04; roofs (upward) 0.10, 0.04; floors (downward) 0.17, 0.04.. Checked November 5, 2026
  2. [2]Gebäudeenergiegesetz (GEG), Anlage 7: Höchstwerte der Wärmedurchgangskoeffizienten bei Änderung. Bundesministerium der Justiz, gesetze-im-internet.de. Residential buildings, when an element is renewed: external walls 0.24 W/(m²K); pitched roofs, top-floor ceilings and walls to unheated roof spaces 0.24; flat roofs 0.20; walls and ceilings to unheated rooms or ground 0.30.. Checked November 5, 2026