Respuesta corta
Whole-house rate in cfm = 0.03 × floor area in ft² + 7.5 × (bedrooms + 1). A 2,000 ft² home with 3 bedrooms needs 60 + 30 = 90 cfm, about 42 l/s or 153 m³/h, running continuously.
Calcúlelo
Calculadora de ventilación
Aire de renovación para la vivienda y caudal de los extractores de baño y cocina.
Calculadora de ventilación →Whole-house ventilation
ASHRAE 62.2-2016 sets the total rate from two parts: one for the building, 0.03 cfm per ft² of floor area, and one for the people, 7.5 cfm each. The number of people is taken as the number of bedrooms plus one.
- Q (cfm) = 0.03 × A (ft²) + 7.5 × (Nbr + 1).
- In metric: 1 cfm = 0.472 l/s = 1.70 m³/h; 0.03 cfm per ft² is about 0.15 l/s per m².
Bathrooms and kitchens
On top of the whole-house rate, ASHRAE 62.2 asks for local exhaust where moisture and smells are made. Each room can run on demand, at a higher rate, or continuously at a lower one.
| Room | On demand | Continuous |
|---|---|---|
| Bathroom or toilet | 50 cfm (25 l/s) | 20 cfm (10 l/s) |
| Enclosed kitchen | Vented range hood 100 cfm (50 l/s) | 5 air changes per hour of the kitchen volume |
| Open kitchen | Vented range hood 100 cfm (50 l/s) | no continuous rate listed |
Worked examples
- 2,000 ft², 3 bedrooms: 0.03 × 2,000 + 7.5 × 4 = 60 + 30 = 90 cfm.
- 120 m², 3 bedrooms: 120 m² is 1,292 ft², so 38.8 + 30 = 68.8 cfm, which is 32 l/s or 117 m³/h.
- For comparison, the European heat-load method assumes at least 0.5 air changes per hour in living rooms. For the 120 m² home with 2.5 m ceilings, 300 m³ × 0.5 = 150 m³/h.
The two numbers answer different questions: ASHRAE 62.2 sets the fresh air people need, the 0.5 air changes are what the heating has to warm. Both are useful when you size a ventilation unit and its heating load.
Preguntas
How many cfm of ventilation does a house need?
0.03 cfm per ft² plus 7.5 cfm per person, counting bedrooms plus one. 90 cfm for a 2,000 ft² home with three bedrooms.
What size bathroom fan do I need?
50 cfm if it runs when the bathroom is used, or 20 cfm if it runs all the time (ASHRAE 62.2).
How strong should a range hood be?
At least 100 cfm vented to the outside for the ASHRAE 62.2 minimum.
How many air changes per hour is that?
It depends on the volume. For a 120 m² home with 2.5 m ceilings, 117 m³/h is about 0.4 air changes per hour.
Calcúlelo
Calculadora de ventilación
Aire de renovación para la vivienda y caudal de los extractores de baño y cocina.
Calculadora de ventilación →Fuentes
- [1]2016 Update for ASHRAE 62.2 (D. Prather, 2016-11-02). ACCA HVAC Blog. Whole-dwelling ventilation rate of ANSI/ASHRAE 62.2-2016: Qtot = 0.03 × Afloor + 7.5 × (Nbr + 1), in cfm, with Afloor in ft² and Nbr the number of bedrooms.. Comprobado el 11 de noviembre de 2026
- [2]BSC-01-2013 Ventilation Rates (J. Lstiburek, Building Science Symposium 2013). Building Science Corporation. ASHRAE 62.2 rate described as 7.5 cfm per person plus 0.03 cfm per ft² of conditioned area; occupancy is the number of bedrooms plus one.. Comprobado el 11 de noviembre de 2026
- [3]ANSI/ASHRAE Addendum e to ANSI/ASHRAE Standard 62.2-2022, Tables 5-1 and 5-2. ASHRAE. Local exhaust. Demand controlled: vented range hood 100 cfm (50 L/s) for enclosed and open kitchens; bathroom or toilet room 50 cfm (25 L/s). Continuous: enclosed kitchen 5 air changes per hour of the kitchen volume; bathroom or toilet room 20 cfm (10 L/s). No continuous rate is listed for an open kitchen.. Comprobado el 11 de noviembre de 2026
- [4]Heizlast-Berechnung nach DIN EN 12831, Teil 1 (E. Held, SBZ Monteur 01/2005). SBZ Monteur. Minimum air change of 0.5 per hour for living rooms in the European heat load method, shown for comparison.. Comprobado el 11 de noviembre de 2026