How much ventilation a home needs: ASHRAE 62.2 in plain numbers

Airtight homes keep heat in but also keep moisture, smells and pollutants in. The US ventilation standard ASHRAE 62.2 turns the question "how much fresh air" into one short formula, plus fixed rates for bathrooms and kitchens.

Aggiornato il 18 novembre 2026

In breve

Whole-house rate in cfm = 0.03 × floor area in ft² + 7.5 × (bedrooms + 1). A 2,000 ft² home with 3 bedrooms needs 60 + 30 = 90 cfm, about 42 l/s or 153 m³/h, running continuously.

Calcola

Ventilation calculator

Fresh air for the whole home and the right bathroom and kitchen fans.

Ventilation calculator →

Whole-house ventilation

ASHRAE 62.2-2016 sets the total rate from two parts: one for the building, 0.03 cfm per ft² of floor area, and one for the people, 7.5 cfm each. The number of people is taken as the number of bedrooms plus one.

BedroomBathroomLivingKitchenFresh airExhaustExhaust
Fresh air comes in where people live and sleep; stale and moist air leaves from the bathroom and the kitchen.
  • Q (cfm) = 0.03 × A (ft²) + 7.5 × (Nbr + 1).
  • In metric: 1 cfm = 0.472 l/s = 1.70 m³/h; 0.03 cfm per ft² is about 0.15 l/s per m².

Bathrooms and kitchens

On top of the whole-house rate, ASHRAE 62.2 asks for local exhaust where moisture and smells are made. Each room can run on demand, at a higher rate, or continuously at a lower one.

Local exhaust (ASHRAE 62.2-2022, Tables 5-1 and 5-2)
RoomOn demandContinuous
Bathroom or toilet50 cfm (25 l/s)20 cfm (10 l/s)
Enclosed kitchenVented range hood 100 cfm (50 l/s)5 air changes per hour of the kitchen volume
Open kitchenVented range hood 100 cfm (50 l/s)no continuous rate listed

Worked examples

  • 2,000 ft², 3 bedrooms: 0.03 × 2,000 + 7.5 × 4 = 60 + 30 = 90 cfm.
  • 120 m², 3 bedrooms: 120 m² is 1,292 ft², so 38.8 + 30 = 68.8 cfm, which is 32 l/s or 117 m³/h.
  • For comparison, the European heat-load method assumes at least 0.5 air changes per hour in living rooms. For the 120 m² home with 2.5 m ceilings, 300 m³ × 0.5 = 150 m³/h.

The two numbers answer different questions: ASHRAE 62.2 sets the fresh air people need, the 0.5 air changes are what the heating has to warm. Both are useful when you size a ventilation unit and its heating load.

Domande

How many cfm of ventilation does a house need?

0.03 cfm per ft² plus 7.5 cfm per person, counting bedrooms plus one. 90 cfm for a 2,000 ft² home with three bedrooms.

What size bathroom fan do I need?

50 cfm if it runs when the bathroom is used, or 20 cfm if it runs all the time (ASHRAE 62.2).

How strong should a range hood be?

At least 100 cfm vented to the outside for the ASHRAE 62.2 minimum.

How many air changes per hour is that?

It depends on the volume. For a 120 m² home with 2.5 m ceilings, 117 m³/h is about 0.4 air changes per hour.

Calcola

Ventilation calculator

Fresh air for the whole home and the right bathroom and kitchen fans.

Ventilation calculator →

Fonti

  1. [1]2016 Update for ASHRAE 62.2 (D. Prather, 2016-11-02). ACCA HVAC Blog. Whole-dwelling ventilation rate of ANSI/ASHRAE 62.2-2016: Qtot = 0.03 × Afloor + 7.5 × (Nbr + 1), in cfm, with Afloor in ft² and Nbr the number of bedrooms.. Verificato il 11 novembre 2026
  2. [2]BSC-01-2013 Ventilation Rates (J. Lstiburek, Building Science Symposium 2013). Building Science Corporation. ASHRAE 62.2 rate described as 7.5 cfm per person plus 0.03 cfm per ft² of conditioned area; occupancy is the number of bedrooms plus one.. Verificato il 11 novembre 2026
  3. [3]ANSI/ASHRAE Addendum e to ANSI/ASHRAE Standard 62.2-2022, Tables 5-1 and 5-2. ASHRAE. Local exhaust. Demand controlled: vented range hood 100 cfm (50 L/s) for enclosed and open kitchens; bathroom or toilet room 50 cfm (25 L/s). Continuous: enclosed kitchen 5 air changes per hour of the kitchen volume; bathroom or toilet room 20 cfm (10 L/s). No continuous rate is listed for an open kitchen.. Verificato il 11 novembre 2026
  4. [4]Heizlast-Berechnung nach DIN EN 12831, Teil 1 (E. Held, SBZ Monteur 01/2005). SBZ Monteur. Minimum air change of 0.5 per hour for living rooms in the European heat load method, shown for comparison.. Verificato il 11 novembre 2026